Change to Daylight Savings Time
Date/time data is saved in UTC format. Entries are in double for one hour when
setting back to normal time. In this case, the curve is displayed using both
values. When switching to daylight savings times, no value is displayed in this
hour and the displayed line is straight between the two measured values.
A system message Anomaly is generated when changing times that must be
acknowledged.
Application Examples for Online or Offline Trend
Online Trend: You can create the online trend if the room temperature is too low
and record data for specified period and analyze measured values in a trend curve
directly on the management station.
Offline Trend: Assign the outside temperature to the Trendlog object in the
automation station if you want to calculate energy consumption and need the
outside air temperature series for measured values. You can then manually or
automatically (periodically) upload the recorded temperature data to store in the
management station.