User Guide
Scheduler
7
BACnet Scheduling
159
Siemens User Guide Version 2.1
A6V10415471_en_a_21
Building Technologies 2015-07-15
7. Clear the Default check box.
NOTE: Creating an entry with the default check box checked returns control to
the weekly schedule. For example, you might want to override the schedule for
one hour at 1 P.M., so you create an entry at 1 P.M. with the override value.
Then, you create an entry at 2 P.M. with Default checked. Control will then
return to the weekly schedule at 2 P.M.
8. Select OFF from the drop-down list.
9. Click Save .
The system saves the exception, and the OccupancySchedule for the week
now looks like the following:
7.4.2 BACnet Calendars
Calendars allow you to override a scheduled event. In this sense, you can consider
them as exception schedules, consisting of dates only. When you create a
calendar, you can choose specific dates (January 15), a date range (August 1 –
31), or a week and a day you want the exception to run (third week of the month,
on Wednesday). All calendars are associated with a schedule. If you want to
reduce energy costs in your building during company holidays, for example, you
could create a holiday calendar. On these days, your calendar might command the
system to reduce the output of heating or cooling systems when the building is
unoccupied.