User Guide

6
Remote Notifications
New Remote Notification Workspace
134
Siemens User Guide Version 2.1 A6V10415471_en_a_21
Building Technologies 2015-07-15
possible to reach the groups thresholds.
Other escalation groups are still pending.
Running Sent Sent No replies are required for a group and its recipients.
Aborted Cancelled Acknowledged
Timed out
Cancelled
The operator has stopped the
manual
remote notification.
The status of the recipients that replied does not change.
The status of the recipients that did not reply within the timeout
does not change.
The status of the recipients that replied after the remote
notification is aborted changes to
Acknowledged
..
Completed Acknowledged
Sent
Acknowledged
Timed out
Sent
No replies are required for a group and the related recipients.
Some recipients have replied; other recipients have timed out,
and others still need to reply.
All the groups have reached their response thresholds.
Partially failed Acknowledged
Timed out
Sent
Acknowledged
Timed out
Pending
Some recipients have replied, other recipients have timed out,
and others need to reply.
At least one group did not reach its threshold within the
timeout.
No escalation group is pending.
No replies are required for a group and its recipients.
No Response Timed out Timed out
Acknowledged
The system successfully sent at least one message to the mail
server but none of the recipient groups reached their reply
threshold (different from 0).
No escalation group is pending.
Failed Not Reachable Not Reachable For any reason, the system fails in sending all the messages to
the mail server.
Completed
Partially failed
Failed
Acknowledged
Timed out
Sent
Acknowledged
after timeout
One or more recipients have replied after the timeout.
6.2 New Remote Notification Workspace
When you open RENO Message in the Secondary pane, you can switch to New
Remote Notification workspace. Here you can compose a message, define the
recipients, and send an operator-issued remote notification, meaning one that is
not triggered by an alarm.