User Guide
6
Remote Notifications
Remote Notification Messages Workspace
130
Siemens User Guide Version 2.1 A6V10415471_en_a_21
Building Technologies 2015-07-15
Assisted Treatment – Example of Remote Notification Operating Procedure Step
RENO Messages Toolbar
Icon
Name
Description
Alarm-based notifications
New notifications
Back to
configuration
-
Available only from the
Secondary pane. It lets you
switch to Edit mode to
compose and send a new
(operator-issued) notification.
Start RENO
procedure
Initiate a
manual
remote
notification. This command
becomes unavailable while the
system is sending the
message. It may then become
available again to let you re-
send the notification message.
If available, it lets you send the
notification message again.
Stop RENO
procedure
Aborts a time-delayed
automatic remote notification
or stop monitoring the
message status for a manual
remote notification.
This command is available only
if this option was configured
and the
automatic
remote
notification is time-delayed, or
the
manual
remote notification
is in the
Running
state and the
entire notification is not yet
completed. Once you stop a
notification, you cannot restart
it (the notification status
changes to
Aborted
).
Stop monitoring the message
status.
Stop RENO
procedure
escalation
Stops escalation of the remote notification message for the
selected recipient group.
An escalation is an increase in the number of recipients for a
group. If not enough people in the original group respond, the
notification can then be sent to an additional set of recipients.