User Guide

5
Alarm Management
Overview of Alarm Handling
122
Siemens User Guide Version 2.1 A6V10415471_en_a_21
Building Technologies 2015-07-15
The Assisted Treatment window [ 106] displays on the screen.
1. From the Steps list, select the remote notification step text.
The related application displays in the Default tab of the Primary pane.
2. Depending on the remote notification type (automatic or manual) and
commands availability click:
Start RENO procedure to manually start the remote notification or to
send the remote notification again (either manual or automatic).
Stop RENO procedure to abort an automatic, but time-delayed remote
notification or stop monitoring the message status for a manual remote
notification.
Stop RENO procedure escalation to stop the remote notification
escalation for the selected recipient group.
3.
(Optional)
Select a recipient in the Message Status area to view the message
sent in the Message area.
Depending on the result of the remote notification procedure, the steps status
becomes one of the following:
-
Successful, the remote notification message status is
Completed
.
-
Failed, the remote notification message status is
Aborted
,
Partially failed
or
No Response
but you can mark the step as executed.
-
Failed, the remote notification message status is
Failed
; and you cannot
mark the step as executed.