User Guide

5
113
Siemens User Guide Version 2.1
A6V10415471_en_a_21
Building Technologies 2015-07-15
5.5.9.4 Suspending an Event
You may want to suspend an event, for example, because you have already
selected it and you want to suspend alarm handling as there are other events
waiting to be handled.
Click the event button [ 83] that corresponds to the event being handled.
The event is no longer handled.
NOTE:
If you select an event in Event List while another event is being handled, the
alarm handling for this event is suspended, and the new selected event is
handled.
5.5.9.5 Clearing an Event
Depending on how you are handling an event, you can clear an event from Event
List in one of the following ways:
You have completed Fast or Investigative Treatment.
The event is selected and the event status is Closed.
The suggested action is Suspend event.
Click the event button [ 83].
In Fast Treatment, the event is cleared from Event List.
In Investigative Treatment, the Investigative Treatment window closes and the
event is cleared from Event List.
You have completed Assisted Treatment (all the mandatory steps of an
operating procedure have been executed).
The event is selected and the event status is Ready to be closed.
The Close command is available.
The suggested action is Close event.
1. Click Close .
The event status becomes Closed. The suggested action is Suspend
event.
2. Click the event button [ 83].
The Assisted Treatment window closes and the event is cleared from Event
List.
5.5.9.6 Silencing/Unsilencing a Field Panel
You have selected an event.
The command to
silence
a field panel is available in the event descriptor
[ 84].
Click Silence .
The field panel is silenced.