Configuring alarm routing
Alarms is selected in the core function pane.
1. Select > > Configure alarm routing.
2. Use the following table to make selections in the Configure alarm routing dialog
box.
3. To save your selections, click Apply.
Table 13: Configure alarm routing dialog box.
Setting
Description
Max. number of resend attempts
The maximum number of times the application attempts to send an alarm notification email if the
alarm requires an acknowledgement and it has not yet been acknowledged.
If the object is no longer in alarm, an alarm notification email is not resent even if the alarm
requires an acknowledgement, but it has not yet been acknowledged.
Valid entries are numbers greater than or equal to 0. The default is 3.
Retry interval (minutes)
The number of minutes the application waits before resending an email for an unacknowledged
alarm.
Valid entries are numbers greater than or equal to 1. The default is 15.
9.8 Local settings
This section outlines how to configure local settings, such as language, time, or the
screen brightness for a touch panel.
1. In ABT-SSA, select > Favorite commissioning.
2. Click for the desired item in the list.
3. Click to display the most commonly used parameters.
4. Use the following table to make selections for each item.