Operating Instructions
Table Of Contents
General settings
Configuring alarm routing
75 | 80
Siemens
A6V11211557_enUS_b
Building Technologies
2019-01-15
Table 12: Configure alarm history dialog box.
Setting
Description
Purge if older than
The default setting is 1 year.
● Amount field: Valid entries are numbers greater than 0.
● Unit of measure drop-down list: Days, Weeks, Months, Years or All.
Time for purge
The default setting is Daily, –, –.
If Field 1 is …
Field 2 options
Field 3 options
Daily
–
–
Weekly
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
–
Monthly
Week 1 (Days 1-7)
Week 2 (Days 8-14)
Week 3 (Days 15-21)
Week 4 (Days 22-28)
Week 5 (Days 29-31)
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Time
Displayed in the format selected by the currently logged in user. The default setting is 22:00 or 10:00 PM.
● Field 1: Hours
● Field 2: Minutes
9.7 Configuring alarm routing
The Operation application checks the database once per minute for alarms that need
to be sent. If there are multiple alarm notices for a recipient, they are sent in a single
email.
By default, the application makes three attempts to send an alarm notification email if
the alarm has not been acknowledged. The default interval between each attempt is 15
minutes.