Operating Instructions

Table Of Contents
Trends
Trends tools
61 | 80
Siemens
A6V11211557_enUS_b
Building Technologies
2019-01-15
Setting
Description
Save every check box
Select to record the present value for the selected object(s) at the
defined time interval.
Default: Not selected
Drop-down list
The time interval for data collection.
Default: 15 seconds
Save when value changes check
box
Select to record the present value for the selected object(s) each time
the value changes.
Default: Not selected
Save when value changes more
than field
The amount a value must change before a sample is collected. This
field is only displayed if one or more sampled data objects is numeric
(Analog).
Default: 5
Delete trend data after check box
Select to delete trend samples that are older than the defined number of
months.
Default: Not selected
Delete data interval field
Trend data older than the defined number of months will be deleted.
Default: 12 months
Setting
Description
Name
The name of the export job.
Default: Trend export - [selected location in the building structure]
Select data points
Navigate through the building structure to select objects that currently
have a trend definition.
Send to FTP server check box
Select to export trend samples to the FTP server.
Default: Selected
Send to email recipients check
box
Select to export trend samples to selected email recipients.
Default: Not selected