Indicator
Description
Cause
Value quality
Fault
Indicates a system or process alarm
Transition
Indicates a non-alarm event (object not updated by data
acquisition yet, or a command being processed)
Operating mode
Out of service
Indicates whether the physical input/output has been
decoupled by means of property Out-Of-Service
Overridden
Object overridden by external switch
Life safety
Personal safety (Present priority is 1...3)
Locked
Locked function/object (Present priority is 4...5)
Time delay
Delay is active (Present priority is 6)
Manual switch
Switch is set to manual (Present priority is 7)
Manual Prio 8
Manual state of an object is indicated
Alarm state
In alarm. Alarm not acknowledged.
Not in alarm. Alarm not acknowledged.
In alarm. Alarm acknowledged.
Not in alarm. Alarm acknowledged.
Not in alarm. Reset.