Operating Instructions

Table Of Contents
Overview
User interface
11 | 80
Siemens
A6V11211557_enUS_b
Building Technologies
2019-01-15
Tools and settings
Click to access the tools and settings menus. The options displayed depend on the role of the
currently logged in user.
Full screen is mainly for use with a graphic display. When selected, the browser bar
displays at the top of the screen, but the Status bar (⑥) and the Core function pane (②) do not
display.
Tools provides tasks that are specific to each core function.
Settings configures SMTP, FTP, email recipients, alarm polling, alarm history and alarm
routing, and manages data point integration settings.
Indicator
Description
BACnet object type
Structured view objects
Building
AreaView(Bldg)
Floor
AreaView(Floor)
Room
AreaView (R)
Room segment
AreaView (RSegm)
Central function
AreaView (CenFnct)
Favorite view
FvrView
Network view (Field buses)
NwkView
Network view (Assigned devices,
Discovered devices)
NwkView (AssgnDev, DscvdDev)
Automation station
ASView
Collection
Col (Infrastructure, Device, Third Party)
Application function
FuncView
Value objects
Input value
AI, BI, BlsIn, LgtIn, MI
Output value
AO, BO, BlsOut, EmgLgt, LgtAOut, LgtBOut, MO
Calculated value
ACalcVal, BCalcVal, MCalcVal, PrphDev