Installation Instructions
Table Of Contents
Pharmacy Solution Set Matrix
Requirements based on:
• USP 795: Pharmaceutical Compounding – Nonsterile Preparations (Proposed Revision: March 2018) A6V11517837
• USP 797: Pharmaceutical Compounding – Sterile Preparations (Proposed Revision: July 2018) Rev 1 September 2018
• USP 800: Hazardous Drugs – Handling in Healthcare Settings (Proposed Revision: February 2016) Page 4 of 17
USP 797 Matrix
USP-NF Chapter 797 Requirement
Evaluation
Engineered Services & Solutions
Building System
Information Management
Service Solutions
Environmental Controls
Primary Engineering Controls (PECs)
All Compounded Sterile Preparations (CSPs)
must be prepared in an ISO Class 5
environment. Class 5 standards are achieved
through the use of a PEC or an isolator.
Buffer and Cleanroom Areas
1
PECs need to be located within a buffer or
cleanroom area with at least ISO Class 7 air
quality. An ante-area provides access to the
buffer area and must meet at least ISO 8
standards. Buffer area for CSPs must be at
least 0.02 inches water column (wc) greater
than adjacent spaces.
The anteroom which
provides entry into a buffer room must have:
HEPA-filter-supplied 20 ACPH
Positive pressure of 0.02 inches wc relative
to all adjacent unclassified spaces
ISO Class 8 for CSPs
Workbenches and Barrier Isolators
PECs generally include laminar airflow
workbenches, biological safety cabinets, and
isolators. Compounding facilities must be
designed and controlled to provide a well-lit
and comfortable working environment. The
room must be maintained at a temperature of
20°C or cooler and a humidity below 60% at
all times.
Assessment of current environment:
o Air cleanliness
o Room construction
o Exhaust system
o Supply air
o Cooling system
o Temperature and humidity control
o Differential pressure (D/P) control
and monitoring
Design, installation, and
commissioning of (enhanced) room
controls for the buffer and anteroom
areas to achieve the desired airborne
particle count, air changes per hour
(ACPH), D/P, temperature, and
humidity levels
Custom DXR Lab application for PEC
DXR Lab application that can interlock
with PEC fan and provide shutdown
when flow or pressure is compromised
Particle counter integration when
installed for continuous monitoring
RCM II for monitoring D/P and for
local display of D/P, temperature,
humidity, ACPH, and particle counts
(if available)
Fire alarm system per local codes
Backup to EES (Essential Electrical
System) power per NFPA 99
RCM II provides local indication of
D/P, temperature, humidity, ACPH,
and particle counts.
The Desigo CC workstation serves as
the primary interface into the building
automation system for real-time
monitoring, troubleshooting, control of
building systems, alarm management,
and collection of trend data
(temperature, humidity, pressure,
ACPH, and alarm statuses).
The RENO (Remote Notification
option for Desigo CC) allows
notification of alarm, status, and system
event information for all points
integrated into the system.
Desigo CC provides for the archiving
and reporting of data needed to
demonstrate compliance with
applicable regulations.
Compliance services:
o Clean room testing and
certification
o Cabinet testing and certification
o Calibration
o Training
o Automation service offering for
CMS compliance
Facility information services:
o Environmental reporting and
consulting
o Custom report design and creation
(temperature, humidity, ACPH,
and positive pressurization).
Note: If equipment is integrated,
reports can include refrigerator
and freezer temperatures and
particle counter readings.
o Data archiving and retrieval
o User training
1
If used to prepare only Category 1 CSPs, the PEC may be located in an unclassified area, without a buffer or ante-area. The area must be a segregated compounding area (SCA).