User Manual
Declaration of performance No DOP190209
EN
6 / 70
Siemens Schweiz AG
V01
6 / 70
EN 54-5:2000 + A1:2002
Essential characteristics Section Performance
Response times at high operating temperature (during opera-
tion in dry heat)
5.6 Passed
Manufacturing tolerance 5.8 Passed
Test for detectors from class index S 6.1 Passed
Test for detectors from class index R 6.2 Passed
Operational reliability
Individual alarm indicator 4.4 Passed
Connection of auxiliary devices 4.5 Passed
Monitoring of removable detectors 4.6 Passed
Manufacturer adjustments 4.7 Passed
Setting of response behaviour on site 4.8 Passed
Labelling 4.9 Passed
Technical manual 4.10 Passed
Additional requirements for software-controlled detectors 4.11 Passed
Supply voltage tolerance
Fluctuations in supply parameters 5.7 Passed
Stability of operational reliability, temperature resistance
Cold (during operation) 5.9 Passed
Dry heat (endurance test) 5.10 NPD
Stability of operational reliability, vibration resistance
Impact (during operation) 5.14 Passed
Blow (during operation) 5.15 Passed
Oscillation, sinusoidal (during operation) 5.16 Passed
Oscillation, sinusoidal (endurance test) 5.17 Passed
Stability of operational reliability, moisture resistance
Humid heat, cyclical (during operation) 5.11 Passed
Humid heat, constant (endurance test) 5.12 Passed
Stability of operational reliability, corrosion resistance
Sulphur dioxide (SO
2
) corrosion (endurance test) 5.13 Passed
Stability of operational reliability, electrical stability
Electromagnetic compatibility (EMC), interference immunity
tests (during operation)
5.18 Passed
EN 54-17:2005 + AC:2007
Essential characteristics Section Performance
Performance in the event of fire
Manufacturing tolerance 5.2 Passed
Operational reliability
Requirements 4 Passed
Stability of operational reliability, temperature resistance
Dry heat (during operation) 5.4 Passed
Cold (during operation) 5.5 Passed
Stability of operational reliability, vibration resistance
Impact (during operation) 5.9 Passed
Blow (during operation) 5.10 Passed
Oscillation, sinusoidal (during operation) 5.11 Passed
Oscillation, sinusoidal (endurance test) 5.12 Passed
Stability of operational reliability, air humidity resistance
Humid heat, cyclical (during operation) 5.6 Passed
Humid heat, constant (endurance test) 5.7 Passed
Stability of operational reliability, corrosion resistance
Sulphur dioxide (SO
2
) corrosion (endurance test) 5.8 Passed
Stability of operational reliability, electrical stability