User`s manual

Signal Equalizer Settings for Non Recommended Cable or Unknown
Cable Lengths,
Continued
Instructions &
Examples
This procedure is for determining the DataNET Signal Equalizer Board
settings for other than the recommended cable or if the cable run lengths
are unknown.
Step Action
1. To determine appropriate settings for attenuator boards,
begin by measuring signal levels at the various ports (use
either Option 1 or 2).
Important
The cables should be removed from all but one port at a time.
This allows the one connected port to come on line and
operate, thus allowing measurement of signal level.
2. Sequentially go through the ports, and measure and record
the signal level of the response
Example:
Port # Signal Level
1
1.6 v p-p
2
1.75 v p-p
4
1.25 v p-p
6
4.8 v p-p
8
4.5 v p-p
2000585-001 Installation 39