User`s manual

Site Wiring Requirements, Continued
DataNET Channels
The DataNET channel connections can be either copper wire or fiber
optic cable. The wiring method and cable type for DataNET is dependent
upon the site requirements. For cable requirements see Table 2-1.
The following Table should be used when evaluating or selecting cable
for an existing or new DataNET installation.
Table 2-1:
Recommended DataNET
Cable
Cable Type Vendors & P/N Installation Notes
Fiber Optic
MM 62.5/125; 2 Fiber
Conductors
SEA P/N 1270002-002
Industry Available from
Multiple Vendors
New Installation as an
alternative to copper
cable
Max distance from
Analyzer to Hub or
between Hubs 1520
meters (5000 ft)
2- Conductor Copper
Wire
SEA P/N 1686002-001
Belden P/N 9182
for
Belden Armored Cable
order
SEA P/N 1680000-002
Recommended for
Single Channel
Max distance from
Analyzer to Hub or
between Hubs 1520
meters (5000 ft)
4-Conductor Copper
Wire
SEA P/N 1681000-003
Belden P/N SSD1743
Recommended for Dual
Channel
Max distance from
Analyzer to Hub or
between Hubs 1520
meters (5000 ft)
Ethernet Cat 5
Unshielded Twisted
pair (UTP)
SEA P/N 1681003-006
Industry Available from
Multiple Vendors
Recommended for
short distances or
within shelters.
Max distance from
analyzer to hub or
between hubs 600
meters (2000 ft)
20 Installation 2000585-001