User`s manual

DataNET Hub Specifications, Continued
DataNET Option, Standard
Cable
Cable connection by Belden 9182 (single pair) or Belden
SSD1743 (two pairs) or equivalent; two pairs of wires are
required to support redundancy
Two pairs of cable is required to support redundancy
Shielded cable or unshielded cable in conduit is required for
conformance to CE certified installation
Two part connectors with screw-terminals provided for field
connection
DataNET Option, Fiber Optic
Cable
Fiber optics connection by 62.5 multi-mode cable corresponding
to 10BaseFL Ethernet specification
Two pairs of fibers are required to support redundancy
Type ST mating connectors provided for field connection
Approximately 3 mbps base transmission rate; uses dedicated
transmission technique that does not require collision detection to
achieve high data throughput efficiency
Fiber Optic Coupler Two (Tx, Rx) ST-Style Connectors
Ethernet Option Each Hub half has an Ethernet connector but only the ‘A’ Hub half is
active.
Cable connection by 10BaseT (twisted pair) AT&T D-inside wire
(DIW & PDS, IBM Type 3, Category 3 or 5 data) cable
Shielded cable or unshielded cable in conduit is required for
conformance to CE certified installation
8-pin RJ-45 connector (female) provided
10 mbps standard Ethernet
Maximum length to adapter concentrator/hub 100m (328 ft)
Serial Port
Standard RS-232 port for attachment of a laptop computer, for
configuring DNH IP Addresses and troubleshooting.