Inspection
Check that the product is in a good condition.
Compare the pressure indicated on the pressure gauge with the values given on the
cylinder's instruction label, taking into account the room temperature when performing
the check.
If the pressure is 10% (or more) below the temperature-adjusted nominal pressure,
replace the cylinder.
The frequency of the product inspection is subject to applicable local regulations.
For more
information, refer to the maintenance documentation.
Safety measures
Before handling, dismantling or transport, place the cylinder in safe position.
After an actuation
Make the installation safe.
Replace the cylinder with an identical cylinder.
Refer to the maintenance instructions to obtain detailed procedures.
Regulatory check
Depends on the current regulations in the country. Observe ADR regulation in case of road
transportation.