User Manual

Technical data
Power supply
Operating voltage (M, L+)
DC 24 V = ± 20 %
Safety extra-low voltage SELV per
IEC/EN / DIN EN / UL 60950-1 or
NEC Class 2 or
LPS per IEC/EN / DIN EN / UL 60950-1
DC 24 V = Direct current only!
Protective earth
Cross section min. 2.5 mm
2
/14AWG
The protective earth connection must be connected on
the installation side with the building grounding system
(PE).
Power consumption
Max. 1.8 A / 43 W at DC 24 V =
Typically 510 mA / 13 W
Internal fusing
None
Function data
Hardware information
Processor
Intel Celeron N2807, dual core, 1,58 GHz
RAM
4 GB DDR3L
SSD
128 GB, 2.5" SATA
Software information
OS
Linux
Response to a power outage
Loss of power buffering
20 ms
BIOS backup battery
Connections
Power: Pluggable screw terminals,
Cu-wire or Cu-strand with wire end sleeve
0.75 to 2.5mm
2
(28 to 14 AWG)
Cu-strand without wire end sleeve
0.75 to 2.5mm
2
(28 to 14 AWG)
Stripping length
6...7.5 mm (0.24...0.29 in)
Screwdriver
Slot screws with a ca. 3 mm blade
Max. tightening torque
0.6 Nm (0.44 lb ft)
Ethernet interfaces
Plug
2 x RJ45, screened
Interface type
10 / 100 / 1000 Mbps, IEEE 802.3 compatible
Galvanic isolation of system neutral M
Yes
USB interface (Unused)
Plug
Type A
1 x USB3.0
4 Gbps, 900 mA
3 x USB 2.0
0.48 Gbps, 500 mA
Max. load for all USB consumers
Max. 6 W
Galvanic isolation of system neutral M
No