This product information sheet describes the behavior of the above mentioned inverters
(Firmware version V3.0), that is not described in the associated documentation, edition
06/2007, Firmware version 3.0.
All inverters
If in sensorless vector control (SLVC) one of the following problems appears
• motor does not ramp up
• setpoint jumps at low frequencies at ramp down
• motor does not ramp down to 0 Hz even if torque limit is set to 0
• the calculated motor temperature (P0621 > 0) shown in r0035 is implausible
this can be caused by faulty values for both, stator and motor cable resistance.
Try the following to solve the problem:
• disconnect the motor from the feeder cable,
• measure the stator resistance and the motor cable resistance with an ohmmeter or
better with a wheatstone bridge
• put the values in P0350 (stator resistance) and P0352 (cable resistance),
• then perform "calculation of motor parameters" again with P0340 = 3.
If you don' not get feasible values measuring the stator resistance, use the equivalent
circuit data of the motor (this can be can be provided by the motor manufacturer) and
write it into the respective parameters (fig 6.1 in Function Manual) or reduce the stator
resistance in 5 % steps and perform "calculation of motor parameters" again with
P0340 = 3.
Fail-safe inverters
If activating SS1 or SLS, this triggers the STO signal as a pulse. This STO pulse has no
influence on the SS1 or SLS function and can be ignored.
CU240S PN
If in HW config of STEP 7 a different telegram type is selected from the telegram type
selected in P0922 in the inverter, the inverter trips - by fault - with F00452 (belt failure). If
this fault occurs then check the telegram set in HW config and P0922.
Power Modules PM260
With Power Modules PM260 "motor temperature identification" (P0621) only works with a
KTY sensor.
SINAMICS G120
SINAMICS G120D
SIMATIC ET 200S FC
SIMATIC ET 200pro FC