Operating instructions

Commissioning (software)
2.7 Commissioning modes
Control Units CU240S
2-48 Operating Instructions (Compact), 04/2006, A5E00766042B AA
Parameter Action/Description (Factory setting: bold) Setting
Insert the MMC to the inverter - for the parameter set to be uploaded, perform the following
steps:
P0010 = 30 Commissioning parameter*
0: Ready
1: Quick commissioning
2: Inverter
30: Factory setting
95: Commissioning the fail-safe functions (CUs with Safety-Integrated functions only)
P0804 = ? Select Clone file
0: clone00.bin
99: clone99.bin
P0802 = 2 Transfer data from EEPROM
0: Disabled
1: Start OP Transfer
2: Start MMC Transfer
If the upload has been completed successfully, P0010 and P0802 will be set to 0 and the
"RDY" LED is on.
If the upload has failed, F0061 (MMC-PS not fitted) will be displayed, LED "SF" (red) is on.
In this case insert an MMC and attempt another upload.
After a successful upload remove the MMC from the upload inverter.
Manual Download of a parameter set with an MMC
Note
The following important restrictions should be considered when using the download
procedure:
During the download the inverter will not react to any commands.
Once the download procedure has started, it cannot be interrupted.
During download, if the data is not compatible with the inverter, the default values for
those parameters will be written into the inverter memory.
If the download fails, the inverter will not function correctly.