Operating instructions
Commissioning (software)
2.7 Commissioning modes
Control Units CU240S
2-48 Operating Instructions (Compact), 04/2006, A5E00766042B AA
Parameter Action/Description (Factory setting: bold) Setting
Insert the MMC to the inverter - for the parameter set to be uploaded, perform the following
steps:
P0010 = 30 Commissioning parameter*
0: Ready
1: Quick commissioning
2: Inverter
30: Factory setting
95: Commissioning the fail-safe functions (CUs with Safety-Integrated functions only)
P0804 = ? Select Clone file
0: clone00.bin
…
99: clone99.bin
P0802 = 2 Transfer data from EEPROM
0: Disabled
1: Start OP Transfer
2: Start MMC Transfer
If the upload has been completed successfully, P0010 and P0802 will be set to 0 and the
"RDY" LED is on.
If the upload has failed, F0061 (MMC-PS not fitted) will be displayed, LED "SF" (red) is on.
In this case insert an MMC and attempt another upload.
After a successful upload remove the MMC from the upload inverter.
Manual Download of a parameter set with an MMC
Note
The following important restrictions should be considered when using the download
procedure:
• During the download the inverter will not react to any commands.
• Once the download procedure has started, it cannot be interrupted.
• During download, if the data is not compatible with the inverter, the default values for
those parameters will be written into the inverter memory.
• If the download fails, the inverter will not function correctly.