Operating instructions
Commissioning (software)
2.7 Commissioning modes
Control Units CU240S
2-34 Operating Instructions (Compact), 04/2006, A5E00766042B AA
2.7.8.6 Flow chart - Digital output functions
Assigning digital output functions
Parameter Description (Factory setting: bold) Setting
P0731 = 52:3 BI: function of digital output 0 (DO0), defines the source for digital output 0
Terminal 18: DO0, NC/Terminal 19: DO0, NO/Terminal 20: DO0, COM
52:3 Inverter fault active
P0732 = 52:7 BI: function of digital output 1,defines the source for digital output 1
Terminal 21: DO1, NO/Terminal 22: DO1, COM
52:7 Inverter warning active
P0733 = 0:0 BI: function of digital output 2, defines the source for digital output 2
Terminal 23: DO0, NC/Terminal 24: DO0, NO/Terminal 25: DO0, COM
0:0 Digital output disabled
P0748 Invert digital outputs
Bits 0, 1 and 2 can be used to invert the signals of digital outputs 0, 1 and 2
2.7.8.7 Flow chart - Frequency setpoint
Frequency setpoint set
Parameter Description (Factory setting: bold) Setting
P1000 = ? Selection of frequency setpoint
0: No main setpoint
1: MOP setpoint (P1031 … P1040)
2: Analog setpoint (P0756 … P0762), factory setting for CU240S
3: Fixed frequency (P1001 … P1023)
6: Fieldbus (P2050 … P02091), factory setting for CU240S DP and CU240S DP-F, not
available with CU240S)
7: Analog setpoint 2
10: Additional setpoint (1 = MOP) + Main setpoint (0 = No main setpoint)
11: Additional setpoint (1 = MOP) + Main setpoint (1 = MOP)
12: Additional setpoint (1 = MOP) + Main setpoint (2 = Analog setpoint)
…
62: Additional setpoint (6 = Fieldbus) + Main setpoint (2 = Analog setpoint)
63: Additional setpoint (6 = Fieldbus) + Main setpoint (3 = Fixed frequency)
…