Operating instructions
Commissioning (software)
2.7 Commissioning modes
Control Units CU240S
Operating Instructions (Compact), 04/2006, A5E00766042B AA
2-19
33
3 3
33
Figure 2-6 Example of typical motor rating plate
2.7.3 Quick Commissioning - flow chart
Performing Quick Commissioning via OP
For applications using V/f (P1300 = 0 [default]) or Flux Current Control (FCC) (P1300 = 1 or
6), quick commissioning can be accomplished by setting the following paramters:
Enter the motor frequency P0100
Enter the rating label data P0304, P0304, P0305, P0307, P0310 and P0311
Command and setpoint sources P0700, P1000
Minimum and maximum frequency P1080, P1082
Ramp-up and ramp-down times P1120, P1121
Closed-loop control mode P1300
Motor data identification P1900 = 3
For applications using Vector Control (P1300 = 20 … 23), the parameters in the following
flow chart should be set and used:
Parameters designated with an "*" offer more settings than are actually shown here. Refer to
the Parameter list for additional settings.