Installation manual

Technical specifications
Power Module PM240
Hardware Installation Manual, 07/2009, A5E00807525B AD
73
Table 6- 8 Frame Sizes E, 3 AC 380 V … 480 V, ± 10%
filtered 0BE33-0AA0 0BE33-7AA0
Order No.
unfiltered
6SL3224-
0BE33-0UA0 0BE33-7UA0
kW 30 37 Rated power based on HO-
loading
hp 40 50
filtered kW 1.04 1.2 Power loss
unfiltered kW 0.99 1.2
Rated input current (HO) 73 90
Rated output current (HO) 60 75
Rated input current (LO) 88 105
Rated output current (LO) 75 90
Fuse 100 125
110 110 Required cooling air flow
240 240
25.0 … 35.0 25.0 … 35.0 Input cable /
Output cable
AWG 3 … 2 3 … 2
kg 23 23 filtered
lb 50.7 50.7
kg 16 16
Weight
unfiltered
lb 35.3 35.3
Table 6- 9 Frame Sizes F, 3 AC 380 V … 480 V, ± 10%
filtered 0BE34-5AA0 0BE35-5AA0 0BE37-5AA0
Order No.
unfiltered
6SL3224-
0BE34-5UA0 0BE35-5UA0 0BE37-5UA0
kW 45 55 75 Rated power based on HO-
loading
hp 60 75 100
filtered kW 1.5 2.0 2.4 Power loss
unfiltered kW 1.4 1.9 2.3
Rated input current (HO) 108 132 169
Rated output current (HO) 90 110 145
Rated input current (LO) 129 168 204
Rated output current (LO) 110 145 178
Fuse 160 200 250
150 150 150 Required cooling air flow
320 320 320
35.0 … 120 35.0 … 120 35.0 … 120 Input cable /
Output cable
AWG 2 … 4/0 2 … 4/0 2 … 4/0
kg 52 52 52 filtered
lb 115 115 115
kg 36 36 36
Weight
unfiltered
lb 79.5 79.5 79.5