Installation manual
Technical specifications
Power Module PM240
70 Hardware Installation Manual, 07/2009, A5E00807525B AD
Power Module specifications
CAUTION
High Overload (HO) and Light Overload (LO) input currents
The input current at the rated operating point - applies for the short-circuit voltage of the line
supply V
k
= 1% referred to the rated Power Module power and a rated line supply voltage of
400 V without a line reactor. If a line reactor is used, the specified values are reduced.
NOTICE
UL certified Fuses must be used
In order that the system is in compliance with UL, UL certified fuses, circuit-breaker or self
protected combination motor controller must be used.
Table 6- 3 Frame Sizes A, 3 AC 380 V … 480 V, ± 10%
Order No. unfiltered 6SL3224- 0BE13-7UA0 0BE15-5UA0 0BE17-5UA0
kW 0.37 0.55 0.75 Rated power based on HO-
loading
hp 0.5 0.75 1
Power loss kW 0.097 0.099 0.102
Rated input current (HO) A 1.6 2.0 2.5
Rated output current (HO) A 1.3 1.7 2.2
Rated input current (LO) A 1.7 2.1 2.6
Rated output current (LO) A 1.3 1.7 2.2
Fuse A 10 10 10
l/s 4.8 4.8 4.8 Required cooling air flow
CFM 10 10 10
mm
2
1.0 … 2.5 1.0 … 2.5 1.0 … 2.5 Input cable /
Output cable
AWG 18 … 14 18 … 14 18 … 14
kg 1.2 1.2 1.2 Weight
lb 2.6 2.6 2.6