Operating instructions

Commissioning
5.5 Commissioning using the BOP
Control Units CU240S
Operating Instructions, 10/2007, A5E00766042B AC
59
5.5.1.2 Changing Parameters via BOP
Changing parameter with the BOP
The description below serves as an example that shows how to change any parameter using
the BOP.
Table 5-4 Changing P0003 - parameter access level
Step Result on display
1 Press to access parameters
2 Press until P0003 is displayed
3 Press to display the parameter value
4 Press or to set the required value (set to 3)
5 Press to confirm and store the value
6 All level 1 to level 3 parameters are now visible to the user.
Table 5-5 Changing P0700 an index parameter - setting BOP control
Step Result on display
1 Press to access parameters
2 Press until P0700 is displayed
3 Press to access the parameter value
4 Press or to select index 1
5 Press to display actual set value
6 Press or to the required value
7 Press to confirm and store the value
8 Press until r0000 is displayed
9 Press to return the display to the standard drive display (as defined by the customer)
Note
The BOP sometimes displays "bUSY" when changing parameter values. This means that the
inverter is presently handling another higher-priority task.