Operating instructions
Commissioning
5.4 Message F00395
Control Units CU240S
56 Operating Instructions, 10/2007, A5E00766042B AC
5.4 Message F00395
Description
The message F00395 is displayed to prompt you to check the parameter set. In case of
standard CUs you accept the responsibility for a parameter set by confirming F00395. In
case of fail-safe CUs you have to carry out an acceptance test.
F00395 does not indicate an inverter fault.
Confirming F00395 on standard CUs
For CUs without fail-safe function, you confirm F00395 in one of the following ways:
● Via a factory reset
● Via the function key FN on the BOP
● Digital input or PLC signal (depends on the settings of P0700)
● Setting P7844 = 0
Confirming F00395 on fail-safe CUs
For CUs with fail-safe functions, it is necessary to do an acceptance test to confirm F00395.
For details to the acceptance test (refer to the "Commissioning the Fail-Safe functions"
section in this manual.
You confirm F00395 on fail-safe CUs in the following way:
● P0010 = 30
● P9761 = safety password
● P7844 = 0
● Carry out acceptance test
Procedures which require a release of a parameter set via F00395
A Control Unit indicates F00395 in the following states:
● After the first power ON
● After an automatic download
● After a swap of the Control Unit