Operating instructions
Description
3.5 Factory Settings of the Control Unit
Control Units CU240S
Operating Instructions, 10/2007, A5E00766042B AC
27
Table 3-4 Command sources and their BICO connections with default settings of P0700
CU240S (P0700 = 2) CU240S DP (P0700 = 6)
CU240S DP-F (P0700 = 6)
CU240S PN (P0700 = 6)
CU240S PN-F (P0700 = 6)
Function
Parameter BICO source Parameter BICO source
ON/OFF1 / ON/OFF1 P0840 = 722.0 DI0 P0840 = 2090.0 CW1, Bit 0
ON reverse/OFF1 (not active per default) P0842 = 0.0 --- P0842 = 0.0 ---
First OFF2 source: Coast stop P0844 = 1.0 --- P0844 = 2090.1 CW1, Bit 1
Second OFF2 source: Coast stop P0845 = 19.1 BOP P0845 = 19.1 BOP
First OFF3 source: Quick stop P0848 = 1.0 --- P0848 = 2090.2 CW1, Bit 2
Second OFF3 source: Quick stop P0849 = 1.0 --- P0849 = 1.0 ---
Pulse enable P0852 = 1.0 --- P0852 = 2090.3 CW1, Bit 3
Table 3-5 Fixed frequency command sources and their BICO connections with default settings of P0700
CU240S (P0700 = 2),
CU240S DP (P0700 = 6)
CU240S PN (P0700 = 6)
CU240S DP-F (P0700 = 6)
CU240S PN-F (P0700 = 6)
Function
Parameter BICO source Parameter BICO source
Fixed freq. selection Bit 0 P1020 = 722.3 DI3 P1020 = 722.3 DI3
Fixed freq. selection Bit 1 P1021 = 722.4 DI4 P1021 = 722.4 DI4
Fixed freq. selection Bit 2 P1022 = 722.5 DI5 P1022 = 722.5 DI5
Fixed freq. selection Bit 3 P1023 = 722.6 DI6 P1023 = 0 ---
Table 3-6 Monitoring settings and their BICO connections with default settings of P0700
CU240S (P0700 = 2) CU240S DP (P0700 = 6)
CU240S DP-F (P0700 = 6)
CU240S PN (P0700 = 6)
CU240S PN-F (P0700 = 6)
Function
Parameter BICO source Parameter BICO source
First source for "Fault acknowledge" P2103 = 722.2 DI2 P2103 = 722.2 DI2
Second source for "Fault acknowledge"
(not active per default)
P2104 = 0.0 --- P2104 = 2090.7 CW1, Bit 7
External fault P2106 = 1 --- P2106 = 1 ---
Table 3-7 Factory settings for setpoint source
CU240S (P0700 = 2) CU240S DP (P0700 = 6)
CU240S DP-F (P0700 = 6)
CU240S PN (P0700 = 6)
CU240S PN-F (P0700 = 6)
Source
Parameter BICO source Parameter BICO source
Frequency setpoint r0754[0], [%] AI0+ / AI0- P2050.1 [Hex] PZD from Fieldbus