Operating instructions

Description
3.5 Factory Settings of the Control Unit
Control Units CU240S
26 Operating Instructions, 10/2007, A5E00766042B AC
3.5 Factory Settings of the Control Unit
Factory settings for command and setpoint source
P0700 = 0 is the same as P0700 = 2 or 6 dependent on type of Control Unit.
Note
Setting P0700 = 6 (command source via fieldbus communication) and P1000 = 6 (setpoint
source via fieldbus communication) are not possible with a CU240S.
Setting P0700 = 5 (command source via USS communication) and P1000 = 5 (setpoint
source via USS communication) are not possible with a CU240S DP or a CU240S DP-F.
Table 3-3 Functions of Digital Inputs and Digital Outputs with default settings of P0700
CU240S (P0700 = 2) CU240S DP (P0700 = 6)
CU240S PN (P0700 = 6)
CU240S DP-F (P0700 = 6)
CU240S PN-F (P0700 = 6)
Function
Parameter Source Parameter Source Parameter Source
ON/OFF1 P0701 = 1 DI0 r2090.00 CW1, Bit 0 r2090.00 CW1, Bit 0
Reverse P0702 = 12 DI1 r2090.11 CW1, Bit 11 r2090.11 CW1, Bit 11
Fault acknowledge P0703 = 9 DI2 r2090.07 CW1, Bit 7 r2090.07 CW1, Bit 7
Fixed freq. selector bit0 P0704 = 15 DI3 r2091.00 CW2, Bit 0 r2091.00 CW2, Bit 0
Fixed freq. selector bit1 P0705 = 16 DI4 r2091.01 CW2, Bit 1 r2091.01 CW2, Bit 1
Fixed freq. selector bit2 P0706 = 17 DI5 r2091.02 CW2, Bit 2 r2091.02 CW2, Bit 2
Fixed freq. selector bit3 P0707 = 18 DI6 r2091.03 CW2, Bit 3 --- ---
Drive fault active P0731 = 52.3 DO0 P0731 = 52.3 DO0 P0731 = 52.3 DO0
Drive warning active P0732 = 52.7 DO1 P0732 = 52.7 DO1 P0732 = 52.7 DO1
Note
Digital inputs 7 and 8 and Digital output 2 are disabled per default.