Operating instructions
Description
3.4 Interfaces of the Control Units
Control Units CU240S
Operating Instructions, 10/2007, A5E00766042B AC
25
Terminal Designation Function CU240S;
CU240S DP;
CU240S PN
CU240S DP-F
CU240S PN-F
73 ENC BN Channel B inverting input x x
74 ENC ZP Channel 0 (zero) non-inverting input x x
75 ENC ZN Channel 0 (zero) inverting input x x
The control terminals have a maximum tighten torque of 0.25 Nm (2.2 lbf.in) and a nominal
cross section of 1.5 mm
2
(AWG 14) for cable.
MMC
The MMC provides the ability to store parameter sets or firmware versions of an inverter.
It is recommended that the SINAMICS-MMC (order number: 6SL3254-0AM00-0AA0) is used
for the storage and transfer of parameter sets or firmware versions.
Option port
Via the Option port a PC (using the PC Connection Kit) or a BOP is connected to the
inverter. With a PC the inverter can be easily parameterized using the commissioning tool
STARTER.