Operating instructions

Functions
5.3 Command sources
CU240S and CU240E Control Units, FW 3.2
Operating Instructions, 03/2009, A5E02440075B AA
93
5.3 Command sources
5.3.1 Selecting command sources
Selecting the command source [P0700]
The motor is switched on/off via external inverter control commands. The following command
sources can be used to specify these control commands:
Operator control / display instrument (operator panel)
Digital inputs
Fieldbus
The command sources available depend on the inverter version.
For inverters with a fieldbus interface, the 'fieldbus' (P0700 = 6) is pre-selected as the
command source,
For inverters without a fieldbus interface, the digital inputs (P0700 = 2) are pre-selected
as command source.
Table 5- 13 Parameters, to select the source for the inverter control commands
Parameters Description
P0700 = ... 0: Factory default setting
1: Operator panel
2: Digital inputs (P0701 … P0709), factory setting for an inverter without fieldbus
interface
4: USS at RS 232
5: USS at RS 485 (not available for all inverters)
6: Fieldbus (P2050 … P02091), factory setting for inverters with fieldbus interface.