Operating instructions

Commissioning
4.4 Commissioning with factory settings
CU240S and CU240E Control Units, FW 3.2
Operating Instructions, 03/2009, A5E02440075B AA
55
Parameter Factory setting Meaning of the factory setting Function Access
level
P0309 0 [%] Rated motor efficiency (in accordance with
the rating plate in %) if P0100 = 0, then
P0309 is irrelevant
1
P0310 50 [Hz] Rated motor frequency
(in accordance with the rating plate in Hz)
1
P0311 1395 [rpm] Rated motor speed
(in accordance with the rating plate in rpm)
1
P0335 0 Non-ventilated: Shaft-mounted fan
in the motor
Motor cooling (specify the motor cooling
system)
2
P0625 20 [°C] Ambient temperature of motor 3
P0640 200 [%] Motor overload factor (entered in % referred
to P0305)
2
P0700 2 or 6 2 for non-bus-capable CUs
6 for bus-capable CUs
Select the command source 1
P0727 0 DI0: On / off
DI1: Direction reversal
Control response when the motor starts
(start, stop, reverse)
3
P0970 0 Locked Restore factory settings 1
P1000 2 or 6 2 for non-bus-capable CUs
6 for bus-capable CUs
Select the source of the frequency setpoint
(setpoint input)
1
P1080 0 [Hz] Minimum frequency 1
P1082 50 [Hz] Maximum frequency 1
P1120 10 [s] Ramp-up time 1
P1121 10 [s] Ramp-down time 1
P1300 0 V/f control with linear characteristic Control mode 2
P3900 0 No quick commissioning Completes the quick commissioning 1