Operating instructions

Commissioning
4.4 Commissioning with factory settings
CU240S and CU240E Control Units, FW 3.2
54 Operating Instructions, 03/2009, A5E02440075B AA
4.4.2 Factory setting of the frequency inverter
Default command and setpoint sources
Inverters used in automation solutions have the appropriate fieldbus interfaces. These
inverters are preset in the factory so that the appropriate control and status signals can be
exchanged via the fieldbus interface.
Inverters without a fieldbus interface are pre-set in the factory so that the digital and analog
and input output signals are exchanged via terminals.
For instance, if you do not want to control an inverter equipped with a fieldbus interface via
the fieldbus, but instead using switches and pushbuttons that are connected to the digital
inputs, then you must change parameter P0700 as follows.
Table 4- 2 Command and setpoint sources
Parameters Description
P0700 = 2 or 6 Select the command source
2: Digital intputs (P0701 … P0709) (factory setting for CUs without fieldbus interface)
6: Fieldbus (P2050 … P2091), (factory setting for CUs with fieldbus interface)
P1000 = 2 or 6 Select the setpoint source
2: Analog setpoint (factory setting for CUs without fieldbus interface)
6: Fieldbus (factory setting for CUs with fieldbus interface)
Table 4- 3 Factory settings of additional important parameters
Parameter Factory setting Meaning of the factory setting Function Access
level
P0003 1 Access to the most frequently used
parameters
Selecting the user access level 1
P0004 0 All parameters are displayed Parameter filter: filters parameters in
accordance with the functionality
1
P0010 0 Ready to be entered Commissioning parameter 1
P0100 0 Europe [50 Hz] Frequency of the regional supply network
IEC, Europe
NEMA, North America
1
P0300 1 Induction motor Select the motor type (induction motors /
synchronous motor)
2
P0304 400 [V] Rated motor voltage
(in accordance with the rating plate in V)
1
P0305 depends on
the
Power Module
[A] Rated motor current
(in accordance with the rating plate in A)
1
P0307 depends on
the
Power Module
[kW/hp] Rated motor output
(in accordance with the rating plate in
kW/hp)
1
P0308 0 [cos phi] Rated motor power factor (in accordance
with the rating plate in cos 'phi') if P0100 =
1.2, then P0308 is irrelevant
1