Operating instructions

Functions
5.12 Safety functions
CU240S and CU240E Control Units, FW 3.2
212 Operating Instructions, 03/2009, A5E02440075B AA
Function check, "Safely Limited Speed" (SLS)
This check involves the following steps:
Table 5- 99 Function, "Safely Limited Speed" (SLS)
No. Description Status
1. Initial state
The inverter signals "ready for switching on" (P0010 = 0)
No safety faults and alarms
r9772.4 = r9772.5 = 0 (SLS deselected and inactive)
2. Switch on the motor. The motor speed must be higher than the parameterized
safely limited speed, if the machine permits this
3. Check whether the motor involved rotates
4. Select SLS while the ON command is being issued
5. Check the following points:
r9772.4 = 1 (SLS selected)
The motor response depends on the selected mode of the SLS function
SLS mode 0
The drive speed decreases corresponding to the selected ramp time
and then the inverter is subsequently passivated
SLS mode 1
The motor speed decelerates corresponding to the selected ramp
time. The motor then rotates with the parameterized safely limited
speed
SLS mode 2
The inverter is immediately passivated, the motor coasts down
SLS mode 3
The inverter is immediately passivated, the motor coasts down
r9772.5 = 1 (SLS active)
6. Deselect SLS
7. Check the following points:
No safety fault
r9772.4 = r9772.5 = 0 (SLS deselected and inactive)
8. Check whether the drive involved is running. If yes, check the following
points:
The cabling between the Control Unit and Power Module is correct
Correct assignment, drive No. - inverter - Power Module - motor
The hardware can function correctly
Correct wiring of the shutdown paths
Correct parameterization of the SLS function