Operating instructions

Introduction
1.5 Extended adaptation options (parameterization for advanced level personnel)
CU240S and CU240E Control Units, FW 3.2
Operating Instructions, 03/2009, A5E02440075B AA
19
1.5.2 BICO technology: example
Example: Shifting a basic PLC functionality into the inverter
A conveyor system is to be configured in such a way that it can only start when two signals
are present simultaneously. These could be the following signals, for example:
The oil pump is running (the required pressure level is not reached, however, until after
five seconds)
The protective door is closed
The task is realized by inserting free blocks between the digital input 0 and the internal ON
command for the motor and interconnecting them.
&
Index [0]
P2810
Index [1]
r0722.0
r0722.1
r2811
Index [0]
P2849
Timer
T
0
P2850 = 5,0 [s]
r2852
Index [0]
P0840
ON/
OFF1
DI 0
DI 1
P2801[0]P2800
Figure 1-3 Example: Signal interconnection for interlock
Table 1- 13 Parameterizing an interlock
Parameter Description
P0003 = 3 Enable expert access to parameters
P0700 = 2 Select the command source: Digital inputs
P0701 (e.g.) = 99 Enable/"open" digital input 0 (DI0) for BICO parameterization
P0702 (e.g.) = 99 Enable/"open" digital input 1 (DI1) for BICO parameterization
P2800 = 1 Group enable all freely-programmable function blocks (FFB)
P2801 [In000] = 1 Individual enable of the AND function block
P2802 [In000] = 1 Individual enable of the TIMER function block
P2850 = 5.0 Set the TIMER delay time: 5 seconds
P2849 = r0722.0 Connect the status of DI0 to the TIMER input
r0722.0 = Parameter that displays the status of digital input 0.
P2810 [In000] = r2852 Connect the TIMER output to the 1st input of the AND
P2810 [In001] = r0722.1 Connect the status of DI1 to the 2nd AND input
r0722.1 = Parameter that displays the status of digital input 1.
P0840 = r2811 Connect the AND output to the control command ON/OFF1