Operating instructions
Functions
5.11 Operation in fieldbus systems
CU240S and CU240E Control Units, FW 3.2
Operating Instructions, 03/2009, A5E02440075B AA
155
Parameter ID (PKE) and parameter index (IND)
The parameter ID (PKE) is always a 16 bit value. In conjunction with the index (IND), it
defines the parameter to be transferred.
3.(
,1'
3:(
$.
318
630
VW
ZRUG
3DUDPHWHUFKDQQHO
QG
ZRUG
UG
DQG
WK
ZRUG
3.(
,1'
3:(
VW
ZRUG
QG
ZRUG
UG
DQG
WK
ZRUG
6XELQGH[,1'3DJHLQGH[
3DUDPHWHUFKDQQHO
PKE structure IND structure
● The parameter number is encoded in the lower 11 bits (PNU) of the PKE. Since the PNU
can only contain values up to 2000, an offset must also be encoded for parameter
numbers above 2000. The offset is set in the first word of the index (IND) as shown in the
table below.
● Bit 11 (SPM) is reserved and is always 0.
● Bits 12 to 15 (AK) contain the request or response ID.
The meaning of the request ID for request telegrams (master → inverter) is explained in the
following table.
,1'
DGFEI H
IND page index
Table 5- 69 Regulations for setting the PNU
Parameter range Page index Bit Hex value + PNU
a b c d f e 9 8
0000 … 1999 0 0 0 0 0 0 0 0 0x00 0 – 7CF
2000 … 3999 1 0 0 0 0 0 0 0 0x80 0 – 7CF
4000 … 5999 0 0 0 1 0 0 0 0 0x10 0 – 7CF
6000 … 7999 1 0 0 1 0 0 0 0 0x90 0 – 7CF
8000 … 9999 0 0 1 0 0 0 0 0 0x20 0 – 7CF
… … … … … … … … … … …
32.000 … 33.999 0 0 0 0 1 0 0 0 0x8 0 – 7CF
… … … … … … … … … … …
64.000 … 65.999 1 1 1 1 0 1 0 0 0xF4 0 – 7CF