7.3.5 STARTER - setting the Profibus communications
• Communications between the CPU and the SINAMICS G120 must then be
parameterized. To do this, open the screen for the communication settings
using Communication -> Profibus. Select the tab Transmit direction.
• To start, select the Standard-Telegram 350 (350) from Message frame: (1.).
This pre-assigns the telegram.
• Then replace telegram 350 by telegram type Free BICO connection (999) (1.).
Deactivate any possibly active Suppress inactive interconnections function
(2.) and establish the following interconnections (3.):
• PZD 5 = r2131 (Last fault number code)
• PZD 6 = r2132 (First warning number code)