7 Background information
SINAMICS G120 (CU240S DP) Control via PROFIBUS
V1.0, Beitrags-ID: 45288241
25
Copyright © Siemens AG 2010 All rights reserved
7.2.3 FB10, Organization
This block is called-up in absolute terms in OB1 and in turn calls up FC100.
Principle of the FB10
Network Function
1 Calls the FB11 to generate the frequency setpoint
Controls the SINAMICS G120 via the axis-DB, DB1.
Calls the SINAMICS G120 control block FC100.
Provides the feedback signals – incl. error and alarm number
2
This network can be used as template for additional SINAMICS G120 control functions.
3 Controls the signal lamp for fault.
7.2.4 FC100, Control of SINAMICS G120
SINAMICS G120 is controlled using the FC100 via PROFIBUS.
Only signals from the Axis_DB are used to control the block - but no fixed
addresses - this is the reason that instances can be used.
This block can be used in the same way for both a standard and a Safety
SINAMICS G120.
Formal operands of the FC100
Formal operands Type
Description
Nr_Axis_DB IN Number of the Axis-DB generated using UDT1
Internal_Error OUT
Displays an internal error
0 = no error
1 = incorrect Axis-DB type (wrong UDT)
Principle structure of the FC100
Network Function
Opens the Axis_DB specified using the formal operands Nr_Axis_DB.
1
Generates the internal error message.
2
Reads-in the SINAMICS G120 status words, processes these and saves them in the
Axis_DB.
3 Resets internal error messages.
4
Converts frequency and torque setpoint from the Axis_DB (entered in x.x %) into the
SINAMICS G120 format (hex).
5 Enters SINAMICS G120 error and alarm number into the Axis_DB.
6 Sends control words from the Axis_DB to the SINAMICS G120