SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
Description: Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 1st value pair of the characteristic.
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (V, mA) of the 2nd value pair of the characteristic.
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the response threshold for the wire breakage monitoring of the analog inputs.
The unit for the parameter value depends on the set analog input type.
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
p0758[0...1] CU analog inputs characteristic value y1 / CU AI char y1
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9566, 9568, 9576
Min Max Factory setting
-1000.00 [%] 1000.00 [%] 0.00 [%]
p0759[0...1] CU analog inputs characteristic value x2 / CU AI char x2
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9566, 9568, 9576
Min Max Factory setting
-50.000 160.000 10.000
p0760[0...1] CU analog inputs characteristic value y2 / CU AI char y2
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9566, 9568, 9576
Min Max Factory setting
-1000.00 [%] 1000.00 [%] 100.00 [%]
p0761[0...1] CU analog inputs wire breakage monitoring response threshold / CU WireBrkThresh
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9566, 9568
Min Max Factory setting
0.00 20.00 2.00