User Manual
List of parameters
Parameters
1-97
© Siemens AG 2009 - 2013 All Rights Reserved
SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
Description: Displays the status of analog inputs.
Note: AI: Analog Input
Description: Displays the actual input voltage in V when set as voltage input.
Displays the actual input current in mA when set as current input and with the load resistor switched in.
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Dependency: The type of analog input AIx (voltage or current input) is set using p0756.
Refer to: p0756
Note: AI: Analog Input
T: Terminal
Description: Sets the smoothing time constant of the 1st-order low pass filter for the analog inputs.
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note: AI: Analog Input
T: Terminal
Description: Displays the currently referred input value of the analog inputs.
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
r0751.0...9 BO: CU analog inputs status word / CU AI status word
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9566, 9568
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Analog input AI0 wire breakage Yes No -
01 Analog input AI1 wire breakage Yes No -
08 Analog input AI0 no wire breakage Yes No -
09 Analog input AI1 no wire breakage Yes No -
r0752[0...1] CO: CU analog inputs input voltage/current actual / CU AI U/I_inp act
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9566, 9568, 9576
Min Max Factory setting
- - -
p0753[0...1] CU analog inputs smoothing time constant / CU AI T_smooth
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9566, 9568, 9576
Min Max Factory setting
0.0 [ms] 1000.0 [ms] 0.0 [ms]
r0755[0...1] CO: CU analog inputs actual value in percent / CU AI value in %
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9566, 9568, 9576
Min Max Factory setting
- [%] - [%] - [%]