Only sub-index 0 of the specified objects can be mapped.
Note:
As long as A08755 is present, the COB-ID cannot be set to valid.
A08756 CAN: Number of mapped bytes exceeded
Reaction: NONE
Acknowledge: NONE
Cause: The number of bytes of the mapped objects exceeds the telegram size for net data. A max. of 8 bytes is permissible.
Remedy: Map fewer objects or objects with a smaller data type.
A08757 CAN: Set COB-ID invalid
Reaction: NONE
Acknowledge: NONE
Cause: For online operation, the appropriate COB-ID must be set invalid before mapping.
Example:
Mapping for RPDO 1 should be changed (p8710[0]).
--> set p8700[0] = C00006E0 hex (invalid COB-ID)
--> set p8710[0] as required.
--> p8700[0] enter a valid COB-ID
Remedy: Set the COB-ID to invalid.
A08759 CAN: PDO COB-ID already available
Reaction: NONE
Acknowledge: NONE
Cause: An existing PDO COB-ID was allocated.
Remedy: Select another PDO COB-ID.
A08760 CAN: maximum size of the PZD IF exceeded
Reaction: NONE
Acknowledge: NONE
Cause: The maximum size of the PZD interface exceeded.
Fault value 1: receiving
Fault value 2: sending
Deleting the alarm:
- Power Off/On
- Warm restart
- CANopen NMT state change
- reset alarm with p2111
Remedy: Map fewer process data in PDO.
A08800 PROFIenergy energy-saving mode active
Reaction: NONE
Acknowledge: NONE
Cause: The PROFIenergy energy-saving mode is active
Alarm value (r2124, interpret decimal):
Mode ID of the active PROFIenergy energy-saving mode.
See also: r5600 (Pe energy saving mode ID)
Remedy: The alarm automatically disappears when the energy-saving mode is exited.
Note:
After receiving the PROFIenergy command "End_Pause" via PROFINET, the energy-saving mode is exited.
A08802 PROFIenergy not possible to switch off incremental encoder supply
Reaction: NONE
Acknowledge: NONE
Cause: The incremental encoder is used for the closed-loop position control. This means that its power supply cannot be
switched off during the PROFIenergy energy-saving mode, otherwise it would lose its position actual value.
Alarm value (r2124, interpret decimal):
Encoder number