Acknowledging faults
The list of faults and alarms specifies how to acknowledge each fault after the
cause has been remedied.
Table 3-3 Acknowledgement of faults
Acknowledge-
ment
Description
POWER ON The fault is acknowledged by a POWER ON process (switch drive unit off and on again).
Note:
If this action has not eliminated the fault cause, the fault is displayed again immediately
after power-up.
IMMEDIATELY Faults can be acknowledged on one drive object (Points 1 to 3) or on all drive objects
(Point 4) as follows:
1 Acknowledge by setting parameter:
p3981 = 0 --> 1
2 Acknowledge via binector inputs:
p2103
p2104
p2105
BI: 1. Acknowledge faults
BI: 2. Acknowledge faults
BI: 3. Acknowledge faults
3 Acknowledge using PROFIBUS control signal:
STW1.7 = 0 --> 1 (edge)
Note:
These faults can also be acknowledged by a POWER ON operation.
If this action has not eliminated the fault cause, the fault will continue to be displayed
after acknowledgment.
Safety Integrated faults
The "Safe Torque Off" (STO) function must be deselected before these faults are
acknowledged.
PULSE INHIBIT The fault can only be acknowledged with a pulse inhibit (r0899.11 = 0).
The same possibilities are available for acknowledging as described under acknowledge
IMMEDIATELY.