User Manual
Parameters
List of parameters
1-50
© Siemens AG 2009 - 2013 All Rights Reserved
SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
Description: The duty cycles can be overloaded provided that the drive converter is operated with its base load current before
and after the overload. This is based on a load duty cycle of 300 s.
Value: 0: Load duty cycle with high overload for vector drives
1: Load duty cycle with low overload for vector drives
Dependency: Refer to: r3996
Notice: The parameter value is not reset when the factory setting is restored (see p0010 = 30, p0970).
When the power unit use is changed, short-term communication interruptions may occur.
Note: When the parameter is changed, all of the motor parameters (p0305 ... p0311), the technological application
(p0500) and the control mode (p1300) are pre-assigned according to the selected application. The parameter has
no influence when calculating the thermal overload.
p0205 can only be changed to the settings that are saved in the power unit EEPROM.
Description: Displays the rated power unit power for various load duty cycles.
Index: [0] = Rated value
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = Reserved
[4] = Reserved
Dependency: IECdrives (p0100 = 0): Units kW
NEMA drives (p0100 = 1): Units hp
Refer to: p0100, p0205
Description: Displays the rated power unit power for various load duty cycles.
Index: [0] = Rated value
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = Reserved
[4] = Reserved
Dependency: Refer to: p0205
p0205 Power unit application / PU application
PM240
PM250, PM260
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(1, 2) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0
r0206[0...4] Rated power unit power / PU P_rated
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: 14_6 Unit selection: p0100 Func. diagram: -
Min Max Factory setting
- [kW] - [kW] - [kW]
r0207[0...4] Rated power unit current / PU PI_rated
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8014
Min Max Factory setting
- [Arms] - [Arms] - [Arms]