User Manual

List of parameters
Parameters
1-415
© Siemens AG 2009 - 2013 All Rights Reserved
SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
Description: Displays the monitoring status of the fail-safe digital inputs (F-DI).
The F-DIs that are being used by the Safety Integrated functions are displayed.
If the module used has fewer than 3 F-DIs, "Freely available" is displayed for the F-DIs which are not in use.
Dependency: p10006 / p10106
p10022 / p10122
p10023 / p10123
p10026 / p10126
p10030 / p10130
p10031 / p10131
p10050 / p10150
Refer to: r10149
Description: Setting for the transfer and evaluation of failsafe digital inputs (F-DI) via PROFIsafe.
The safe state of the selected F-DIs is transferred to the F-control via PROFIsafe. The F-DIs are monitored for dis-
crepancies. Discrepancy faults can be acknowledged via PROFIsafe.
Dependency: Refer to: p10150
Note: F-DI: Failsafe Digital Input
r10049 SI F-DI monitoring status (processor 1) / SI F-DI status P1
PM240
PM250
PM260
CU240E-2_DP_F
CU240E-2_F
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 F-DI 0 Safety monitored Freely available -
01 F-DI 1 Safety monitored Freely available -
02 F-DI 2 Safety monitored Freely available -
p10050 SI PROFIsafe F-DI transfer (processor 1) / SI Ps F-DI tran P1
PM240
PM250
PM260
CU240E-2_DP_F
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 F-DI 0 processor 1 Transfer No transfer -
01 F-DI 1 processor 1 Transfer No transfer -
02 F-DI 2 processor 1 Transfer No transfer -