User Manual

Parameters
List of parameters
1-412
© Siemens AG 2009 - 2013 All Rights Reserved
SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
Value: 0: Statically active
1: F-DI 0
2: F-DI 1
3: F-DI 2
255: Statically inact
Dependency: Refer to: p10106
Refer to: A01666, A30666
Note: The values "static active" and "static inactive" result in an inactive function of the safe acknowledgment.
F-DI: Failsafe Digital Input
Description: Sets the debounce time for digital inputs.
The debounce time is accepted rounded off to whole milliseconds.
The debounce time acts on the following digital inputs:
- Fail-safe digital inputs (F-DI).
- Single-channel digital inputs (DI).
- Single-channel digital input 5 (DI 5, read back input for the forced checking procedure).
Dependency: Refer to: p10117
Note: Example:
Debounce time = 1 ms: Fault pulses of 1 ms are filtered; only pulses longer than 2 ms are processed.
Debounce time = 3 ms: Fault pulses of 3 ms are filtered; only pulses longer than 4 ms are processed.
The debounce result can be read in r10051.
Description: Sets the fail-safe digital input (F-DI) for the "STO" function.
Value: 0: Statically active
1: F-DI 0
2: F-DI 1
3: F-DI 2
255: Statically inact
Dependency: Refer to: p10122
Note: If value = 0:
No terminal assigned, safety function always active.
If value = 255:
No terminal assigned, safety function always inactive.
F-DI: Failsafe Digital Input
STO: Safe Torque Off
p10017 SI digital inputs debounce time (processor 1) / SI DI t_debounceP1
PM240
PM250
PM260
CU240E-2_DP_F
CU240E-2_F
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.00 [ms] 100.00 [ms] 1.00 [ms]
p10022 SI STO input terminal (processor 1) / SI STO F-DI P1
PM240
PM250
PM260
CU240E-2_DP_F
CU240E-2_F
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 255 0