User Manual
List of parameters
Parameters
1-411
© Siemens AG 2009 - 2013 All Rights Reserved
SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
Index: [0] = Reserved
[1] = Computing time utilization
[2] = Reserved
[3] = Reserved
[4] = Reserved
[5] = Largest total utilization
[6] = Reserved
[7] = Reserved
Dependency: Refer to: F01054, F01205
Note: Re index 1:
The value shows the total computing time load of the system.
Re index 5:
The total utilization is determined using all sampling times used. The largest total utilization is mapped here. The
sampling time with the largest total utilization is displayed in r9979.
Total utilization:
Computing time load of sampling time involved including load from higher-priority sampling times (interrupts).
Description: Diagnostics parameter to display additional information for internal software errors.
Note: Only for internal Siemens troubleshooting.
Description: Sets the monitoring time for the discrepancy for the digital inputs.
The signal states at the two associated digital inputs (F-DI) must assume the same state within this monitoring time.
Dependency: Refer to: p10102
Note: F-DI: Failsafe Digital Input
Description: Select a fail-safe digital input for the signal "acknowledge internal event" (internal fault).
The falling edge at this input resets the status "internal event" in the drives.
The rising edge at this input acknowledges any existing discrepancy errors.
r9999[0...99] Software error internal supplementary diagnostics / SW_err int diag
Access level: 4 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
p10002 SI discrepancy monitoring time (processor 1) / SI discrp t_mon P1
PM240
PM250
PM260
CU240E-2_DP_F
CU240E-2_F
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
1.00 [ms] 2000.00 [ms] 500.00 [ms]
p10006 SI acknowledgement internal event F-DI (processor 1) / SI ackn int evt P1
PM240
PM250
PM260
CU240E-2_DP_F
CU240E-2_F
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 255 0