User Manual
Parameters
List of parameters
1-406
© Siemens AG 2009 - 2013 All Rights Reserved
SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
Note: Rounding effects can occur in the last decimal place of the parameterized time.
The debounce time is rounded to whole milliseconds. It specifies the maximum duration of a fault pulse at the fail-
safe digital inputs with no reaction/influence on the selection or deselection of the Safety Basic Functions.
Example:
Debounce time = 1 ms: Fault pulses of 1 ms are filtered; only pulses longer than 2 ms are processed.
Debounce time = 3 ms: Fault pulses of 3 ms are filtered; only pulses longer than 4 ms are processed.
Description: Displays the supported Safety Integrated monitoring functions.
Processor 2 determines this display.
Dependency: Refer to: r9771
Note: STO: Safe Torque Off
Description: Displays the supported Safety Integrated monitoring functions.
Processor 2 determines this display.
Dependency: Refer to: r9771
Note: STO: Safe Torque Off
r9871 SI common functions (processor 2) / SI common fct P2
PM240
PM250
PM260
CU240E-2
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2804
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 STO supported via terminals Yes No 2804
r9871 SI common functions (processor 2) / SI common fct P2
PM240
PM250
PM260
CU240E-2_DP_F
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2804
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 STO supported via terminals Yes No 2804
02 Extended Functions supported (p9501 > 0) Yes No 2804
04 Extended Functions PROFIsafe supported Yes No -
05 Extended Functions integrated in drive sup-
ported (p9601.2 = 1)
Yes No -
06 Basic Functions PROFIsafe supported Yes No -
07 Extended Functions encoderless supported Yes No -
11 Extended Functions SDI supported Yes No -
12 Extended Functions SSM encoderless sup-
ported
Yes No -