SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
Dependency: Refer to: p9799, r9898
Description: Sets the checksum for the Safety Integrated parameters checked using checksums on processor 1 (setpoint check-
sum).
Dependency: Refer to: r9798, p9899
Description: Sets the enable signals for the safety functions integrated in the drive and the type of selection on processor 1.
Not all of the settings listed below will be permissible, depending on the Control Unit and Power Module being used:
0000 hex:
Safety functions integrated in the drive inhibited (no safety function).
0001 hex:
Basic functions are enabled via onboard terminals (permissible for r9771.0 = 1).
0004 hex:
Extended functions are enabled via onboard terminals (permissible for r9771.5 = 1).
0008 hex:
Basic functions are enabled via PROFIsafe (permissible for r9771.6 = 1).
0009 hex:
Basic functions are enabled via PROFIsafe onboard terminals (permissible for r9771.6 = 1).
000C hex:
Extended functions are enabled via PROFIsafe (permissible for r9771.4 = 1).
000D hex:
Extended functions are enabled via PROFIsafe and basic functions via onboard terminals (permissible for r9771.4
= 1).
Dependency: Refer to: p9601, r9871
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: A change only becomes effective after a POWER ON.
STO: Safe Torque Off
p9799 SI setpoint checksum SI parameters (processor 1) / SI setp_chksm P1
PM240
PM250
PM260
CU240E-2
CU240E-2_DP
CU240E-2_DP_F
CU240E-2_F
CU240E-2_PN_F
CU240E-2 PN
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2800
Min Max Factory setting
0000 hex FFFF FFFF hex 0000 hex
p9801 SI enable functions integrated in the drive (processor 2) / SI enable fct P2
PM240
PM250
PM260
CU240E-2
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Enable STO via terminals (processor 2) Enable Inhibit 2810