Example:
Debounce time = 1 ms: Fault pulses of 1 ms are filtered; only pulses longer than 2 ms are processed.
Debounce time = 3 ms: Fault pulses of 3 ms are filtered; only pulses longer than 4 ms are processed.
Description: Sets the time interval for carrying out the forced checking procedure and testing the Safety shutdown paths.
Within the parameterized time, STO must have been de-selected at least once. The monitoring time is reset each
time that STO is de-selected.
Dependency: Refer to: A01699
Note: STO: Safe Torque Off
Description: Displays the time remaining before dynamization and testing of the safety shutdown paths (forced checking proce-
dure).
Dependency: Refer to: A01699
Description: Setting to start the required copy function.
After starting, the corresponding parameters are copied from processor 1 to processor 2.
Once copying is complete, the parameter is automatically reset to zero.
p9659 SI forced checking procedure timer / SI FCP Timer
PM240
PM250
PM260
CU240E-2
CU240E-2_DP
CU240E-2_DP_F
CU240E-2_F
CU240E-2_PN_F
CU240E-2 PN
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2810
Min Max Factory setting
0.00 [h] 9000.00 [h] 8.00 [h]
r9660 SI forced checking procedure remaining time / SI frc chk remain
PM240
PM250
PM260
CU240E-2
CU240E-2_DP
CU240E-2_DP_F
CU240E-2_F
CU240E-2_PN_F
CU240E-2 PN
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [h] - [h] - [h]
p9700 SI copy function / SI copy function
PM240
PM250
PM260
CU240E-2
CU240E-2_DP
CU240E-2_DP_F
CU240E-2_F
CU240E-2_PN_F
CU240E-2 PN
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95), U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0000 hex 00D0 hex 0000 hex