User Manual

List of parameters
Parameters
1-365
© Siemens AG 2009 - 2013 All Rights Reserved
SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
Note: The signal source to be searched is set in p9484 (BICO-coded).
The search result is contained in r9482 and r9483 and is specified by the count (r9485) and the first index (r9486).
Description: Sets the enable signals for the safe motion monitoring.
Dependency: Refer to: F01682, F01683
Note: For bit 30 = 1, PROFIsafe telegram 900 must be configured in the F host.
A change only becomes effective after a POWER ON.
F-DI: Failsafe Digital Input
SDI: Safe Direction
SLS: Safely-Limited Speed
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
Description: Sets the enable signals for the safe motion monitoring.
Dependency: Refer to: F01682, F01683
Note: For bit 30 = 1, PROFIsafe telegram 900 must be configured in the F host.
A change only becomes effective after a POWER ON.
F-DI: Failsafe Digital Input
SDI: Safe Direction
SLS: Safely-Limited Speed
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
p9501 SI Motion enable safety functions (processor 1) / SI Mtn enable P1
PM240
PM250
PM260
CU240E-2_DP_F
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 0000 0000 0000 0000 0000
0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Enable SI Motion Enable Inhibit -
16 Enable SSM hysteresis and filtering Enable Inhibit 2823
17 Enable SDI Enable Inhibit 2824
30 Enable F-DI in PROFIsafe telegram Enable Inhibit -
p9501 SI Motion enable safety functions (processor 1) / SI Mtn enable P1
PM240
PM250
PM260
CU240E-2_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 0000 0000 0000 0000 0000
0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Enable SI Motion Enable Inhibit -
17 Enable SDI Enable Inhibit 2824