Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Re bit 00:
If the OFF1 or the OFF3 ramp-down time is too low, or there is an insufficient clearance between the SSM limit
speed, and the shutdown speed, then it is possible that the "speed under limit value" signal does not change to 1,
because no speed actual value below the SSM limit was able to be identified before pulse cancellation. In this case,
the OFF1 or the OFF3 ramp-down time or the clearance between the SSM limit speed and shutdown speed must
be increased.
Note: SDI: Safe Direction
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
Re bit 00:
For bit = 1 and with the SSM safety function activated, the following applies:
- During pulse suppression, monitoring is switched off and the feedback signal has a 0 signal level.
For bit = 0 and with the SSM safety function activated, the following applies:
- Monitoring continues during pulse suppression. The feedback signal last displayed before pulse suppression is
kept and the system goes into the STO state.
Re bit 08:
For bit = 1 and with the SDI safety function activated, the following applies:
- During pulse suppression, monitoring is switched off and the status signal indicates inactive.
For bit = 0 and with the SDI safety function activated, the following applies:
- Monitoring continues during pulse suppression. The status signal indicates active and the system goes into the
STO state.
Description: Sets the behavior of safety functions and their feedback during pulse suppression in encoderless operation.
Dependency: Refer to: C01711
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Re bit 00:
If the OFF1 or the OFF3 ramp-down time is too low, or there is an insufficient clearance between the SSM limit
speed, and the shutdown speed, then it is possible that the "speed under limit value" signal does not change to 1,
because no speed actual value below the SSM limit was able to be identified before pulse cancellation. In this case,
the OFF1 or the OFF3 ramp-down time or the clearance between the SSM limit speed and shutdown speed must
be increased.
Note: SDI: Safe Direction
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
Re bit 00:
For bit = 1 and with the SSM safety function activated, the following applies:
- During pulse suppression, monitoring is switched off and the feedback signal has a 0 signal level.
For bit = 0 and with the SSM safety function activated, the following applies:
- Monitoring continues during pulse suppression. The feedback signal last displayed before pulse suppression is
kept and the system goes into the STO state.
Re bit 08:
For bit = 1 and with the SDI safety function activated, the following applies:
- During pulse suppression, monitoring is switched off and the status signal indicates inactive.
For bit = 0 and with the SDI safety function activated, the following applies:
- Monitoring continues during pulse suppression. The status signal indicates active and the system goes into the
STO state.
p9309 SI Motion behavior during pulse suppression (processor 2) / SI Mtn behav IL P2
PM240
PM250
PM260
CU240E-2_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 0000 1111 1111 bin
Bit field: Bit Signal name 1 signal 0 signal FP
08 SDI during pulse suppression and sensor-
less
Becomes inactive Remains active -